ALLTEMP 24-ICM1503 - Oil Primary Control - 45 Sec

Be the first to review this product

Oil Primary Control - Intermittent Ignition - 45 Sec Safety Timing

 

Availability: In stock

$227.87

ALLTEMP 24-ICM1503 - Oil Primary Control - 45 Sec

Double click on above image to view full picture

Zoom Out
Zoom In

More Views

Additional Information

Brochures & Specific Sheets


Stock Code 24-ICM1503
Brand ALLTEMP
Family Oil Primary Control - Intermittent Ignition
Cross Refefence Carlin: 48245 - Tempstar/Heil: 1147017 - White Rodgers: 668-401
Honeywell: R8184G4009, R8184G1138, R8184G1427, R8184G4025

Features

• Controls oil burner, oil valve (if desired) and the ignition transformer in response to a call for heat .

• Solid state flame sensing circuit .

• LED on terminal strip indicates system lockout.

• Enclosed safety switch with external reset button.

• Mounts on standard 4" x 4" junction box; select models may be mounted directly on burner housing.

• 69-45610 Cadmium Sulfide Flame Detector and 24 VAC thermostat required.

• Direct replacement for popular competitive models.

Specifications

Ignition Type: Intermittent

Timing, Safety Switch: 15, 30 or 45 seconds

Mounting Bracket: For mounting on a standard 4" × 4" junction box or direct mounting on burner housing.

Electrical Rating; Contacts (full load):

7.4 A @ 120 VAC; 3.7 A @ 240 VAC

Electrical Rating; Contacts (locked rotor):

44.4 A @ 120 VAC; 22.2 A @ 240 VAC

Dimensions:

• 4 3/8 in. high x 4 1/8 in. wide x 2 1/2 in. deep

• 111 mm high x 104 mm wide x 64 mm deep

Temperature Range: -30°F to +130°F

Approvals • Underwriters Laboratories Inc