Additional Information
Stock Code | FCS003 |
---|---|
Brand | Air Force 1 |
Family | AC Current Switch |
Overload | 200% (< 200% of the rated cross-core current) |
Switch Size | Maximum Switch Rating: 120Vac, 2.5Amp |
Length (in) | 3.937 inch / 100mm |
Width (in) | 1.122 inch / 28mm |
Height (in) | 1.85 inch / 47mm |
Start Temp. (Min) | 32°F/ 0°C |
Start Temp. (Max) | 122°F/ 50°C |
Material | UL 94V-0 flammability rated ABS, insulation class 600 V |
UL Listed | CSA, cCSAus listed |
Case Quantity | 1 |
Notes | For additional options and special quantity discounts, please contact our sales department 1-(855)-296-9508 x 101 or send email to cs@bulbspro.com |
Cross Refefence | Greystone CS-325-HC |
The series FCS003 current switch was designed for monitoring AC. By sensing AC, this device controls AC load on motor, relay, lighting, fan, and applicably monitored circuit, together with contactor. Input passing through current range 1.2--40A, and maximum voltage load up to 120V/2.5A. Delay module was Incorporated into the circuit for optional 5, 10, 15 minutes and zero time delays on action.
With its high overload, accuracy, isolation, safety, low power consumption and strong interference resistance ability, this device has been already widely used in industrial automation.
- Simple construction, High performance divides in split-and solid core housings
- Adjustable trip point, Precise current trip point setting
- Low set point, Minimum trip point as low as 0.5 A, no need for multiple wraps of conductor through the sensor, even loads as small 1/5 HP
- Small size, Fits easily inside small enclosures
- Status LED, Status LED available for easy setups and local indication.
Original Factory Specification:
- Power-supply None, self-powered
- Amperage Range 1.2 to 40A continuous
- Set point range 1.2 to 40A continuous
- Conduct current 0.5±0.2A
- Dimensions (47×100×28.5)mm
- Switch state: Normally open
- Output Rating 2.5A @ 120VAC
- AC load frequency 10-200Hz
- Hysteresis ≤ 1%
- Accuracy 10%
- Repeatability 100%
- Power consumption ≤ 1W
- Response time: <200ms
- Leakage current ≤ 1mA
- Temperature limit 32 to 122℉ (0 to 50℃)
- Humidity limits 10 to 95% RH (none-condensing).
- Enclosure Rating UL 94V-0 flammability rated ABS, insulation class 600 V.
- Maximum overload 200% (< 200% of the rated cross-core current)