Hammond CT800A - Instrument Transformer - Indoor Toroidal - 600V - 5A Secondary

Be the first to review this product

Hammond CT800A - Instrument Transformer - Indoor Toroidal - 600V - 5A Secondary - Current Ratio (Pri. / Sec.) : 800:5 - 0.3% - 1.2% Accuracy - 5-50 VA Burden

 

Availability: In stock

$155.30

Hammond CT800A - Instrument Transformer - Indoor Toroidal - 600V - 5A Secondary

Double click on above image to view full picture

Zoom Out
Zoom In

More Views

Additional Information

Brochures & Specific Sheets


Stock Code CT800A
Brand Hammond
Family Instrument Transformers
Length (in) 6.75"
Width (in) 1.75"
Height (in) 5.25"
Voltage (V) 600V
Amperage 5A Secondary
UPC 62398095296
Weight (lb.) 2 lbs
UL Listed RoHS, CSA, UL
Case Quantity 1
Notes For additional options and special quantity discounts, please contact our sales department 1-(855)-296-9508 x 102 or send email to cs@bulbspro.com

Features

  • Toroidal design.
  • Supplied with 24" insulated secondary leads, terminated with crimped ring connectors.
  • Suitable for use with bare (uninsulated) primary conductor in circuits up to 600 V (4 KV Hi pot); or at higher voltages when a suitably insulated conductor is used.
  • All units have 5 A secondary for use with standard AC ammeters with 5 A movements.
  • Two hole mounting bracket on all models.
  • UL E227616 volume #1 file number X0DW2

 

Application Data
To obtain current measurement:
1.Pass the wire carrying the current to be measured through the window of the CT transformer (acting as a primary winding).
2.Connect the CT secondary to an ammeter with a 5 A movement.

For higher accuracy or higher VA burden rating:
1.Choose a CT with a primary which is a multiple of the required primary rating and which has the accuracy or VA burden you require.
2.Loop the wire carrying the current to be measured through the window a number of times equal to the multiple. This "winding" will reduce the ratio back to required primary rating.
        ◦Example "A": To obtain an accuracy of 1.2% at 10VA burden with a ratio of 100:5, use a CT400 and loop 4 primary turns through the window.
        ◦Example "B": To obtain a 25:5 ratio, use a CT75 with 3 primary turns to yield 2% accuracy or a CT50 with 2 primary turns to yield 3.2% accuracy.