Additional Information
Stock Code | DMED110T1MID |
---|---|
Brand | Lovato |
UPC | 8013975188729 |
Voltage (V) | 230VAC |
Amperage | 40A |
Amp Rating | 40A |
Phase | Single Phase |
UL Listed | EAC , RCM , MID |
Notes | HS Code: 90283011 |
Cross Refefence | Conformity: EN50470-1 EN50470-3 TR 50579 |
General characteristics
The DME series energy meters, MID certified, are needed for billing purposes between electricity supplliers and consumers and for energy consumption measurement in directly connected single-phase installations.
MID is the Measuring Instruments Directive of the European Union; instruments must be certified accordingly whenever used for monetary transactions in this territory.
Operational characteristics
– Nominal supply voltage: 230VAC
– Voltage range: 187-264VAC 50Hz
– Direct connection
– Maximum current: 40A for DME D100/110 T1 MID; 63A for DME D120 T1 MID
– Measurement of 14 electrical parameters for DME D110/120 T1 MID
– Active energy measurement and accuracy: Class B (EN 50470-3)
– Reactive energy measurement and accuracy: Class 2 (IEC/EN 62053-23)
– LCD meter:
• With 5+1 digit count for DME D100/110 T1 MID
• Backlight with 6+1 digit count for DME D120 T1 MID
– Metrological LED with pulse emission for consumption indication
– Clearable partial energy measurements (except for DME D100 T1 MID)
– One output: pulse for DME D100 T1 MID; programmable static for other types
– Modular housing, 1module for DME D100/110 T1 MID; 2 module for DME D120 T1 MID
– Sealable terminal blocks, standard supplied
– EN protection degree: IP40 on front; IP20 at terminals.
Certifications and compliance
Certifications obtained: MID Class B, certifications per module B (type tests) and per module D (production conformity).
Compliant with standards: EN 50470-1, EN 50470-3.
Multi-measurements:
- Total and partial active energy
- Total and partial reactive energy
- Voltage
- Current
- Active and reactive power
- Power factor
- Frequency
- Total and partial hour counter
- Average active power (calculation on every last 15 minutes)
- Maximum demand.