Additional Information
Stock Code | FSP302G |
---|---|
Brand | Edwards |
Family | Fire Protection Equipment |
Voltage (V) | 24VDC |
Amperage | 0.5A |
Color | Grey |
Mounting | Surface |
UL Listed | ULC |
Fire Alarm Control Panel
Standard Features
• Front panel programming
• Compatible with CleanMe® devices, which advises when dirty
• 1, 3, 5 and 10 initiating device circuits (IDC)
• 1, 2 or 4 signal circuits (NAC)
• Optional Class A IDC & NAC circuits
• Supports EC, C2M, EDW and 6200 Series detectors
• One person device testing (audible or silent)
• Combination waterflow and supervisory IDC
• Optional fire department module or integrated dact/dialer
• Optional serial bus annunciators and relays
Application
FireShield Plus provides smoke and fire detection, occupant notification and off-premises signaling for small to medium sized buildings.
The FireShield single-zone panel has one initiating device circuit (IDC) and one notification appliance circuit (NAC). The IDC can be configured for alarm, with or without alarm verification.
Each IDC on the 3, 5 and 10 zone can be configured for one of eight operating modes. The modes are:
• Alarm - without smoke detector verification
• Alarm - with smoke detector verification and instant activation of contact devices
• Waterflow alarm - no retard
• Waterflow alarm - with 15 second retard
• Combination waterflow (no retard) and supervisory
• Combination waterflow (retard) and supervisory
• Supervisory (latching)
• Monitor - for monitoring devices other than alarm or supervisory such as fire doors or fire dampers
NACs can be individually configured for one of three outputs. These are Genesis, Continuous or Temporal. The Genesis selection eliminates the need to install a Genesis Signal Master.
When configured for Genesis notification appliances the Alarm Silence function will silence any Genesis audible appliance but Genesis strobes will remain active until the panel is reset. Both the horns and strobes on Genesis notification appliances will be synchronized across all NACs when the Genesis mode is selected.
Overview
The FireShield Plus fire alarm family consists of 1, 3, 5 and 10 zone conventional fire alarm control panels, an integrated DACT/Dialer, serial annunciator modules and serial remote relay modules. All of these components are microprocessor controlled. The FireShield family is ideal for both new and retrofit installations.
FireShield incorporates features designed to simplify installation, operation and maintenance. These include front panel programming, one person walk testing, selectable IDC and NAC types.
FireShield is powerful enough to meet the demands of today’s installations. The FSP101 single zone power supply provides 1.0 amp of current for notification appliances (0.1 amps can be used for auxilary current). The 3, 5 and 10 zone panel power supplies provide 4.25 amps of current. 3.5 amps can be used for notification appliances and 0.5 amps can be used as auxiliary current. The 10 zone panel will support an additional 3.25A when an optional second transformer (P/N F-XTR120) is installed in the panel.
The 5 and 10 zone control panels can be configured for Class B and Class A operation.
The 1 and 3 zone control panels are configured for Class B operation only.
Remote Annunciator and Relays
The serial bus standard on FireShield models FSP302, FSP502 and FSP1004 is another installation time saver. This circuit allows the connection of Remote System Indicators. Remote Zone Indicators and Remote Relay Modules over a four-wire circuit (data and power). Annunciator and relay modules can be installed up to 1000 feet from the panel on 18-gauge wire.