Additional Information
Stock Code | 24-ICM1501 |
---|---|
Brand | ALLTEMP |
Family | Oil Primary Control - Intermittent Ignition |
Cross Refefence | Honeywell: R8184G4066, R8184G1161, R8184G1294 |
Features
• Controls oil burner, oil valve (if desired) and the ignition transformer in response to a call for heat .
• Solid state flame sensing circuit .
• LED on terminal strip indicates system lockout.
• Enclosed safety switch with external reset button.
• Mounts on standard 4" x 4" junction box; select models may be mounted directly on burner housing.
• 69-45610 Cadmium Sulfide Flame Detector and 24 VAC thermostat required.
• Direct replacement for popular competitive models.
Specifications
Ignition Type: Intermittent
Timing, Safety Switch: 15, 30 or 45 seconds
Mounting Bracket: For mounting on a standard 4" × 4" junction box or direct mounting on burner housing.
Electrical Rating; Contacts (full load):
7.4 A @ 120 VAC; 3.7 A @ 240 VAC
Electrical Rating; Contacts (locked rotor):
44.4 A @ 120 VAC; 22.2 A @ 240 VAC
Dimensions:
• 4 3/8 in. high x 4 1/8 in. wide x 2 1/2 in. deep
• 111 mm high x 104 mm wide x 64 mm deep
Temperature Range: -30°F to +130°F
Approvals • Underwriters Laboratories Inc