Lovato ATLDPS1 - DUAL POWER SUPPLY AUTOMATIC SWITCHING MODULE - 110/230VAC CONFIGURABLE

Be the first to review this product

Lovato ATLDPS1 - DUAL POWER SUPPLY MODULE FOR MEASUREMENT AND CONTROL OF VOLTAGES PRESENT AT SUPPLY INPUTS TO POWER MOTORISED CIRCUIT BREAKERS/CHANGEOVER SWITCHES - 110/230VAC CONFIGURABLE

 

Availability: In stock

$760.32

Lovato ATLDPS1 - DUAL POWER SUPPLY AUTOMATIC SWITCHING MODULE - 110/230VAC CONFIGURABLE

Double click on above image to view full picture

Zoom Out
Zoom In

More Views

Additional Information

Brochures & Specific Sheets


Stock Code ATLDPS1
Brand Lovato
UPC 8013975214541
Voltage (V) 110/230VAC
UL Listed EAC , cULus , RCM
Notes HS Code: 85389091

General characteristics

ATL DPS1 is capable of measuring and controlling voltages at its inputs selecting the most ideal to connect to the output. It is suitable to supply motorised circuit breakers and changeover switches in automatic switching systems of 2 three phase supply lines.
The two voltage inputs of the module are independent and insulated; each is capable of supplying the internal measuring circuit managed by the microcontroller.
It reduces the number of components and improves installation safety.

Main ATL DPS1 features include:
– Voltage value selectable via bypass terminals
– Minimum and maximum voltage tripping thresholds
– 2 single phase L+N inputs
– 1 single phase L+N output
– L1 priority line
– Use with motorised control units powered at 110VAC or 230VAC
– Output voltage monitoring
– Internal relay self-diagnosis
– Indicating LEDs for abnormal conditions and status of inputs and outputs.

Operational characteristics

– Rated supply voltage: 110...230VAC configurable
– Frequency: 50/60Hz
– Input voltage range: 80…300VAC
– Voltage tripping thresholds min / max: 80% and 120% of preset value
– 2 line inputs L1-L2: Single phase, between phase and neutral
– Current output: 4A max.
– Priority line: L1 when both input values are within limits
– Fixed delay time between line switching: 0.5s
– 4 status indication LEDs for voltage of each line within limits, voltage present at output, relay output anomaly
– Mounting: 35mm DIN rail (IEC/EN 60715) or screw-type by means of removable clips
– Modular housing, 3 module
– IEC degree of protection: IP40 on front; IP20 at rear.

Certifications and compliance

Certifications obtained: cULus, EAC, RCM.
Compliant with standards: IEC/EN 61010-1, IEC/EN 61010-2, IEC/EN 61000-6-2, IEC/EN 61000-6-4, IEC/EN 60947-1, IEC/EN 60947-6-1, UL508 and C22.2 n° 14.