Skip to Main Content »

Search Site
Your shopping cart is empty

All Prices are in Canadian Dollars

Edwards FSP502G - Fire Protection Equipment - Five Zone Fire Alarm Control Panel - 24VDC - 0.5A - Grey

Be the first to review this product

Edwards FSP502G - Fire Protection Equipment - Five Zone Fire Alarm Control Panel - 24VDC - 0.5A - Grey


* Please note the lead time for this item is around 8-10 weeks

 

Availability: No

$861.88

Edwards FSP502G - Fire Protection Equipment - Five Zone Fire Alarm Control Panel - 24VDC - 0.5A - Grey

Double click on above image to view full picture

Zoom Out
Zoom In

More Views

Additional Information

Brochures & Specific Sheets


Stock Code FSP502G
Brand Edwards
Family Fire Protection Equipment
Voltage (V) 24VDC
Amperage 0.5A
Color Grey
Mounting Surface
UL Listed ULC

Fire Alarm Control Panel

Standard Features

• Front panel programming
• Compatible with CleanMe® devices, which advises when dirty
• 1, 3, 5 and 10 initiating device circuits (IDC)
• 1, 2 or 4 signal circuits (NAC)
• Optional Class A IDC & NAC circuits
• Supports EC, C2M, EDW and 6200 Series detectors
• One person device testing (audible or silent)
• Combination waterflow and supervisory IDC
• Optional fire department module or integrated dact/dialer
• Optional serial bus annunciators and relays

Application

FireShield Plus provides smoke and fire detection, occupant notification and off-premises signaling for small to medium sized buildings.

The FireShield single-zone panel has one initiating device circuit (IDC) and one notification appliance circuit (NAC). The IDC can be configured for alarm, with or without alarm verification.

Each IDC on the 3, 5 and 10 zone can be configured for one of eight operating modes. The modes are:

• Alarm - without smoke detector verification
• Alarm - with smoke detector verification and instant activation of contact devices
• Waterflow alarm - no retard
• Waterflow alarm - with 15 second retard
• Combination waterflow (no retard) and supervisory
• Combination waterflow (retard) and supervisory
• Supervisory (latching)
• Monitor - for monitoring devices other than alarm or supervisory such as fire doors or fire dampers

NACs can be individually configured for one of three outputs. These are Genesis, Continuous or Temporal. The Genesis selection eliminates the need to install a Genesis Signal Master.

When configured for Genesis notification appliances the Alarm Silence function will silence any Genesis audible appliance but Genesis strobes will remain active until the panel is reset. Both the horns and strobes on Genesis notification appliances will be synchronized across all NACs when the Genesis mode is selected.

Overview

The FireShield Plus fire alarm family consists of 1, 3, 5 and 10 zone conventional fire alarm control panels, an integrated DACT/Dialer, serial annunciator modules and serial remote relay modules. All of these components are microprocessor controlled. The FireShield family is ideal for both new and retrofit installations.

FireShield incorporates features designed to simplify installation, operation and maintenance. These include front panel programming, one person walk testing, selectable IDC and NAC types.

FireShield is powerful enough to meet the demands of today’s installations. The FSP101 single zone power supply provides 1.0 amp of current for notification appliances (0.1 amps can be used for auxilary current). The 3, 5 and 10 zone panel power supplies provide 4.25 amps of current. 3.5 amps can be used for notification appliances and 0.5 amps can be used as auxiliary current. The 10 zone panel will support an additional 3.25A when an optional second transformer (P/N F-XTR120) is installed in the panel.

The 5 and 10 zone control panels can be configured for Class B and Class A operation.

The 1 and 3 zone control panels are configured for Class B operation only.

Remote Annunciator and Relays

The serial bus standard on FireShield models FSP302, FSP502 and FSP1004 is another installation time saver. This circuit allows the connection of Remote System Indicators. Remote Zone Indicators and Remote Relay Modules over a four-wire circuit (data and power). Annunciator and relay modules can be installed up to 1000 feet from the panel on 18-gauge wire. 


Write Your Own Review

Only registered users can write reviews. Please, log in or register

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.