Additional Information
Stock Code | RGK600 |
---|---|
Brand | Lovato |
UPC | 8013975207642 |
Voltage (V) | 12/24VDC |
UL Listed | EAC , cULus |
Notes | HS Code: 85389091 |
Cross Refefence | Conformity: IEC/EN 61010-1 IEC/EN 61000-6-2 IEC/EN 61000-6-3 UL 508 CSA C22.2 n° 14 |
General characteristics for RGK 600 - RGK 601 - RGK 610 - RGK 700 - RGK 800
– Power supply: 7...33VDC
– VAC inputs: Mains and generator L1-L2-L3-N
– Voltage control for one, two and three phase systems with or without neutral
– Rated measurement voltage:
• 480VAC for RGK 600, RGK 601 and RGK 610
• 600VAC for RGK 700 and RGK 800
– Rated measurement voltage range:
• 100...480VAC for RGK 600, RGK 601 and RGK 610
• 30...600VAC for RGK 700 and RGK 800
– Frequency measurement range: 45-65Hz
– Programmable VT ratio
– Current measurement range (3 PH): 0.050...6A or 0.050...1.2A
– Graphic LCD: 128x80 pixels with backlight
– 1 USB/optical and Wi-Fi port on front for programming
– Engine running detection: “D+”, generator voltage and frequency
– Engine speed inputs: “W” or Magnetic “Pick-up” (RGK 601 excluded)
– 1 CANbus-J1939 port (RGK 600 and RGK 610 excluded)
– 3 analog ohmic inputs for oil pressure, engine temperture and fuel level control
– 1 built-in alarm remote port
– Non-volatile memory for event storage
– Alarm, event and parameter text in 5 languages
– Alarm text customisable (8 alarms)
– Event log
– Modbus-RTU and Modbus-ASCII communication protocols (RGK 600 and RGK 601 excluded)
– Compatible with Synergy and Xpress software
– 1 slot for EXP module (EXP10 10, EXP10 11, EXP10 12) for RGK 610
– 3 slots for EXP modules for RGK 800.
For RGK 700 – RGK 800 only
– PLC logic for inputs, outputs and internal status
– 1 communication port: RS232 for RGK 700; RS485 for RGK 800
– Degree of protection: IEC IP65 on front; suitable for use with UL/CSA Type 4X outdoor enclosure installation.
For RGK 800 only
– Neutral current measurement range: 0.050...6A or 0.050...1.2A
– 400Hz frequency support
– 1 programmable analog input
– Modbus-TCP communication protocol
– Current leakage control towards earth/ground
– Clock-calendar (RTC).
Certifications and compliance
Certifications obtained: UL Listed, for USA and Canada (cULus - File E93601), as Auxiliary Devices - Generator controllers except pending for RGK 610; EAC.
Compliant with standards: IEC/EN 61010-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3, UL 508, CSA C22.2 n° 14.
Synergy and Xpress software, See Section 27.
EXP series expansion modules See Section 28, page 2.