Additional Information
Brochures & Specific Sheets
Stock Code | FW821 |
---|---|
Brand | Maple Armor |
Family | Input-Output Module |
Voltage (V) | 15 to 28 VDC |
Amperage | Standby Current 0.15 mA, Active Current (SLC/DCL) 0.26 mA |
Length (in) | 120mm |
Width (in) | 120mm |
Height (in) | 45mm |
Mounting | FW800 / FW801 Base |
Operates | Max. Line Impedance (Input) 25 Ohms, Max. Line Impedance (Output) 1 Ohm, Max. Impedance for Grounding 6.6 K Ohms, Compatible EOLR FW421 (10K Ohms) |
Wire Gauge | 18-12 AWG |
Start Temp. (Min) | 32°F / 0°C |
Start Temp. (Max) | 120°F / 49°C |
UL Listed | UL, cUL listed |
Notes | It is a UL/ULC listed device according to UL864 and ULC-S527 for Fire Protective Signalling Systems for indoor use. When the output is activated the device red LED will indicate the event condition by blinking longer. When the feedback is activated the device red LED will indicate the event condition by blinking twice. A return to the normal condition will cause the event to disappear and the device LED indicator will return to blinking every 4 seconds. |
The FW821 is an intelligent addressable module and takes one address on the Signalling Line Circuit (SLC) or Data Communication Link (DCL) of the fire alarm control panel.