Skip to Main Content »

Search Site
Your shopping cart is empty

All Prices are in Canadian Dollars

Maple Armor FW337 Notification Output Unit - Support 2 Independent Notification Appliance Circuits - 24Vdc

Be the first to review this product

FW337 is a subassembly for the FW106 FACP (Fire Alarm Control Panel). The NOU supports two independent notification appliance circuits. The circuit topology supports Class A or Class B wiring. The maximum current is 2A per NAC, for a maximum of 4A total per NOU. The address is set by the rotary switch on the board. The valid address range is 1~5.
 

Availability: In stock

Call for price

Maple Armor FW337 Notification Output Unit - Support 2 Independent Notification Appliance Circuits - 24Vdc

Double click on above image to view full picture

Zoom Out
Zoom In

More Views

Additional Information

Brochures & Specific Sheets


Stock Code FW337
Brand Maple Armor
Family Firewatcher Panel 106
Part No FW337 NOU
Voltage (V) 24Vdc
Amperage Standby Current 36mA, Alarm Current 54mA
Length (in) 215mm
Width (in) 55mm
Height (in) 50.3mm
IP Rating IP20
Mounting PCB Card Slot Mounting
Start Temp. (Min) 32°F / 0°C
Start Temp. (Max) 120°F / 49°C
UL Listed It meets the UL864 10thEdition listed standard and the ULC-S527 3rdEdition listed standard and FM.
Notes Relative humidity - Up to 93% @ 90° F (32°C) To be installed in a normal dry indoor environment only

It meets the UL864 10th Edition Listed standard and the ULCS527 3rd Edition Listed standard and FM.