General characteristics for RGK 400SA - RGK 420SA
– Key with 3 positions (OFF, local start, remote start), removable in OFF and remote start position (forRGK420SA)
– Power supply: 7...33VDC
– VAC inputs: Generator L1-L2-L3-N
– Single, two and three phase voltage control
– Rated measurement voltage range: 100...480VLL (3PH+N)
– Programmable VT ratio
– Frequency measurement range: 45...65Hz
– Current input: 1PH, /5A or /1A
– Display: LCD with icons (52x35mm/2.05x1.38”)
– Programming port: IR with support of CX01 (USB) and CX02 (Wi-Fi) dongles
– NFC technology for parameter setup
– Powersave mode
– Inputs: 5 negative + 1 positive for emergency
– Outputs: 5 positive, 2A, protected
– Common pin dedicated to EV and START outputs to be used with emergency push button
– Engine running detection: “D+”, Hz
– Engine speed inputs: “W” or Magnetic “Pick-up”
– 1 analog ohmic input for oil pressure, engine temperature or fuel level control
– Alarm and parameter text in 5 languages
– Customisable alarm text (2 alarms)
– Operating temperature: -30...+60°C
– Parameter configuration by NFC technology with NFC app
– Compatible with Synergy and Xpress software.
General characteristics for RGK 600SA - RGK 601SA - RGK 700SA - RGK 800SA
– Power supply: 7...33VDC
– VAC inputs: Generator L1-L2-L3-N
– Single, two and three phase voltage control
– Rated measurement voltage range:
• 100...480VAC for RGK 600SA and RGK 601SA
• 30...600VAC for RGK 700SA and RGK 800SA
– Programmable VT ratio
– Frequency measurement range: 45...65Hz
– Current input: 3PH, /5A or /1A
– Graphic LCD: 128x80 pixels with backlight
– Programming port: IR with support of CX01 (USB) and CX02 (Wi-Fi) dongles
– Common pin dedicated to EV and START outputs to be used with emergency push button
– Engine running detection: “D+”, Hz
– Engine speed inputs: “W” or Magnetic “Pick-up” (RGK601SA excluded)
– 1 CANbus-J1939 port (RGK 600SA excluded)
– 3 analog ohmic inputs for oil pressure, engine temperature and fuel level control
– 1 built-in alarm remote port
– Non-volatile memory for event storage
– Alarm, event and parameter text in 5 languages
– Customisable alarm text (8 alarms)
– Operating temperature: -30...+70°C.
– Modbus-RTU and Modbus-ASCII protocols
– Compatible with Synergy and Xpress software.
For RGK 700SA – RGK 800SA only
– PLC logic for inputs, outputs and internal status
– 1 communication port: RS232 for RGK 700SA; RS485 for RGK 800SA
– Degree of protection: IEC IP65 on front; suitable for use with UL/CSA Type 4X outdoor enclosure installation.
For RGK 800SA only
– Neutral current measurement range: 0.050...6A or 0.050...1.2A
– 400Hz frequency support
– 1 programmable analog input
– Modbus-TCP communication protocol
– Current leakage control towards earth/ground
– Clock-calendar (RTC)
Certification and compliance
Certifications obtained: UL Listed, for USA and Canada (cULus - File E93601), as Auxiliary Devices - Generator controllers except pending for RGK4...SA; EAC.
Compliant with standards: IEC/EN 61010-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3, UL 508, CSA C22.2 n° 14.
Synergy and Xpress software, NFC app See Section 27.