Philips Bodine B50-CAN - Emergency Ballast - 90 Min. - Operates (1) or (2) T5, T8, T9, T10, T12 Fluoresent Lamps - Dual Voltage 120/347V

Be the first to review this product

The B50-CAN can be used with most 17 - 215 W (2’ - 8’) T8, T9, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving. One- or two-lamp operation may be selected (see Table 1). It is also compatible with most one-, two-, three- and four-lamp electronic, standard, energy-saving and dimming AC ballasts.


When AC power fails, the B50-CAN immediately switches to the emergency mode, operating either one or two lamps at a reduced lumen output for a minimum of 90 minutes. When AC power is restored, the B50-CAN automatically returns to the charging mode

 

Availability: Pre-order in 1-2 weeks

$395.25

Philips Bodine B50-CAN - Emergency Ballast - 90 Min. - Operates (1) or (2) T5, T8, T9, T10, T12 Fluoresent Lamps - Dual Voltage 120/347V

Double click on above image to view full picture

Zoom Out
Zoom In

More Views

Additional Information

Brochures & Specific Sheets


Stock Code B50-CAN
Brand Philips
Family CSA Certified Emergency Lighting Equipment
Part No 511790
Length (in) 13.3" (339mm)
Width (in) 2.4" (60mm)
Height (in) 1.5" (38mm)
Voltage (V) 120/347 VAC, 60 Hz
Input Current 280mA
Wattage (w) 4.0 Watts
Bulb Type Fluorescent Lamps
Switch Type: Test Switch: Single Pole
Lumens (Initial) 1400 Lumens
Battery Back Up Yes
Battery Type: High-Temperature, Maintenance-Free Nickel-Cadmium Battery 7- to 10-Year Life Expectancy
Recharge Time: 24 Hrs
Max. Charge Current 280mA
Operates The B50-CAN can be used with most 17 - 215 W (2’ - 8’) T8, T9, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving.
Start Temp. (Min) 0°C (32°F)
Start Temp. (Max) 55°C (131°F)
Weight (lb.) 3.4 lbs
UL Listed UL, CSA and Code Compliance
Case Quantity 1
Warranty 5 Years (NOT pro-rata)

APPLICATION

The B50-CAN fluorescent emergency ballast works in conjunction with an AC ballast to convert new or existing fluorescent fixtures into emergency lighting. The emergency ballast consists of a high-temperature nickel-cadmium battery, charger and electronic circuitry in one compact red case. The B50-CAN can be used with most 17 - 215 W (2’ - 8’) T8, T9, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving. One- or two-lamp operation may be selected (see Table 1). It is also compatible with most one-, two-, three- and four-lamp electronic, standard, energy-saving and dimming AC ballasts. If used in an emergency-only fixture, no AC ballast is necessary. The B50-CAN is suitable for indoor locations. It is not suitable for air handling heated air outlets or wet, damp or hazardous locations. For information about specific lamp and ballast compatibility, please call the factory.

OPERATION

When AC power fails, the B50-CAN immediately switches to the emergency mode, operating either one or two lamps at a reduced lumen output for a minimum of 90 minutes. When AC power is restored, the B50-CAN automatically returns to the charging mode.

INSTALLATION

The B50-CAN does not affect normal fixture operation and may be used with either a switched or unswitched fixture. If a switched fixture is used, an unswitched hot lead must be connected to the emergency ballast. The emergency ballast must be fed from the same branch circuit as the AC ballast. The B50-CAN may be installed inside, on top of or remote from the fixture. The emergency ballast may be remotely installed up to half the distance the AC ballast manufacturer recommends remoting the AC ballast from the lamp or up to 50 feet, whichever is less. Installation is not recommended with fixtures where the ambient temperature may fall below 0°C.

cUL, CSA and CODE COMPLIANCE

The B50-CAN has been tested per applicable standards and is cUL Listed and CSA Certified for factory or field installation. Emergency illumination time exceeds the National Electrical Code (NEC), Life Safety Code (NFPA-LSC), National Building Code of Canada (NBC), National Fire Code of Canada (NFC) and UL/CSA 90-minute requirements.


B50-CAN

CSA Certified Emergency Lighting Equipment


Specification grade;
One- or two-lamp emergency
illumination

 

Product Summary

  • cUL LISTED/CSA CERTIFIED
    Factory or Field Installation
  • Illumination Time
    90 Minutes
  • Initial Light Output
    1100 - 1400 Lumens
  • Full Warranty
    5 Years (NOT pro-rata)
  • Voltage
    120/347 VAC, 60 Hz
  • AC Input Current
    280 mA
  • AC Input Power Rating
    4.0 Watts
  • Test Switch
    Single Pole
  • Battery
    High-Temperature, Maintenance-Free
    Nickel-Cadmium Battery
    7- to 10-Year Life Expectancy
  • Battery Charging Current
    280 mA
  • Recharge Time
    24 Hour
  • Charging Indicator Light
    LED
  • Temperature Rating (Ambient)
    0°C to +50°C (32°F to 122°F)
  • Dimensions
    13.3" x 2.4" x 1.5"
    (339 mm x 60 mm x 38 mm)
    Mounting Center 12.8" (325 mm)
  • Weight
    3.4 lbs. (1.54 kg)